No.S003 Concrete Podium Position Diagram
Steel base
500 mm-high concrete podium
Prefabricated concrete floor
6058
2940
2940
361
900
2940
1. The horizontal error between concrete podiums must be less than 5 mm.
2. Concrete pads or passages with the bearing capacity meeting local civil
work standards can be built on the field outside the concrete podiums for
access and maintenance.
3. The recommended dimensions of a concrete podium is 900 mm x 900
mm x 500 mm. The concrete podium needs to be verified by the design
institute.