Requesting Parameters Using Modbus - GE DigitalFlow XGS868i Programming Manual

Panametrics steam ultrasonic mass flow transmitter
Table of Contents

Advertisement

Chapter 1. Programming Site Data

1.9.4 Requesting Parameters Using MODBUS

To request specific parameters from the XGS868i via the MODBUS, the control system must enter the appropriate
register number. Only registers 1 through 90 are available for MODBUS communications, while registers 508 through
512 are used by the XGS868i to store the MODBUS parameters. For details, see Table 11 below for a 1-Channel meter
or Table 12 on page 39 for a 2-Channel meter.
Note: If you request Channel2 or Averaged data from a 1-Channel meter, the values will all be zero.
MODBUS
Reg #
Hex Addr
1
2
3
5
7
9
11
13
14
16
18
20
21
23
24
26
28
30
32
34
508
509
510
511
512
38
Table 11: MODBUS Registers for a 1-Channel XGS868i
DPR
Description
0
1"
Clear Ch1 Totalizers"
2
Not Used
4
Velocity
8
Act Volumetric
C
Std Volumetric
10
Fwd Totals
14
Rev Totals
18
#Tot Digits
1A
Mass Flow
1E
Fwd Mass Totals
22
Rev Mass Totals
26
#Mass Tot Digits
28
Timer
2C
Error Code
2E
Sound Speed
32
Density
36
Signal Strength Upstream
3A
Signal Strength Downstream
3E
Temperature
42
Pressure
3F6
2
MODBUS baud rate
3F8
3
MODBUS parity
3FA
4
MODBUS stop bits
3FC
MODBUS meter addr
3FE
RESERVED
Scaling
(decimal places)
Size in Bytes
--
2 (16 bit signed)
--
2 (16 bit signed)
2
4 (2 16-bit int)
#Q DIGITS
4 (IEEE 32 bit)
#Q DIGITS
4 (IEEE 32 bit)
#T DIGITS
4 (2 16 bit int)
#T DIGITS
4 (2 16 bit int)
0
#M DIGITS
4 (IEEE 32 bit)
#MT DIGITS
4 (2 16-bit int)
#MT DIGITS
4 (2 16-bit int)
0
2
4 (2 16-bit int)
0
3
4 (2 16-bit int)
4
4 (2 16-bit int)
1
4 (2 16-bit int)
1
4 (2 16-bit int)
2
4 (2 16-bit int)
3
4 (2 16-bit int)
0
0
0
0
---
DigitalFlow™ XGS868i Programming Manual
2
2
2
2
2
2
2
---