The Mass Flow Option
Use this option to calculate mass flow from a static fluid density. Complete the following steps to enter the static
density of the fluid:
1. From the Advanced Features option menu, highlight and double-click on Mass flow calculation in the center pane.
2. Double-click on Yes to activate Static Density or on No to disable this option. (If you select No, PanaView returns
to the Advanced Features window.)
3. If you select Yes, enter the Fluid Density (0.00001 to 0.100 lb/ft
PanaView returns to the Advanced Features window.
After responding to the above prompt, the meter returns to the Advanced Features window. Click [Exit Page] three
times to return to the Site Edit Menu.
C.6 Entering Data in the Global Menu
Global
The
menu is used to enter information that is not specific to any of the individual channels. Information
programmed via this menu is used to enter several general system parameters (e.g., English or metric units). For meters
with 2 channels, this menu is also used to compute parameters such as the sum, difference or average of the channel 1
and channel 2 signals. When calculating the
Any conflicting data entered in the
The following submenus are included in the
System
- use to specify the units of measure used in calculations
Input/Output
- used to set up error handling and to configure analog inputs and outputs
- used to set up the serial communications port and MODBUS parameters
Comm port
To enter the Global menu, double-click on the Global entry in the left pane of the Site Edit Menu window. Then proceed
to the appropriate section of this chapter for instructions. Refer to Figure 54 on page 141 in Appendix D, PanaView
Menu Maps, and remember to record all programming data in Appendix B, Data Records.
110
,
SUM
DIF
AVE
or
Channel-System
submenu is overridden.
Global
menu:
3
or 0.00001 to 123.18 kg/m
Global-System
readouts, data from the
DigitalFlow™ XGS868i Programming Manual
3
) and click [Next Item].
submenu is used.