Functions
4
Control sequences

4.7.12 Setpoints and sequences

2-pipe applications
Application
2-pipe
2-pipe with
electric heater
2-pipe with
radiator
2-pipe/
2-stage
heating or
cooling
76 | 150
In changeover applications, the Comfort setpoints for heating and cooling
sequence are the same (w).
In 2-pipe applications with electric heater, the Comfort setpoint is either at the first
heating sequence (in heating mode) or at the cooling sequence (in cooling mode).
In 2-pipe applications with radiator, the Comfort setpoint is either at the radiator
sequence (in heating mode) or at the cooling sequence (in cooling mode).
The setpoints for Economy and Protection are below the Comfort setpoints (for
heating) and above the Comfort setpoints (for cooling).
They can be set via P019, P020 (Economy) and P100, P101 (Protection).
Comfort mode
Heating
If P027 = On
1)
W = Setpoint in Comfort mode
W
= Setpoint heating in Economy or Protection mode
HeatEco/Prot
W
= Setpoint cooling in Economy or Protection mode
CoolEco/Prot
YR = Radiator sequence
YE = Electric heater sequence
Cooling
Economy/Protection mode
Heating
A6V11545892_en--_a