Expert Level Parameters With Diagnostics And Test - Siemens RDG200KN Basic Documentation

Room thermostats with knx communications
Hide thumbs Also See for RDG200KN:
Table of Contents

Advertisement

4.15.5 Expert level parameters with diagnostics and test

Name
Expert level
Control settings
P050
Heat P-band Xp
P051
Switching differential heating
P052
Cool P-band Xp
P053
Switching differential cooling
P054
Radiator P-band Xp/switching
differential
P055
Dead zone Comfort mode
P056
Setpoint differential
P057
Integral action time Tn for heating
1)
P058
Integral action time Tn for cooling
1)
P059
H/C changeover switching point
2)
cooling
H/C changeover switching point
P060
2)
heating
P063
Minimum supply air temperature
P064
Maximum supply air temperature
Mode and setpoints
P100
Protection heating setpoint
P101
Protection cooling setpoint
P102
Temporary Comfort mode
3)
P103
Temporary Comfort setpoint
P104
Setpoint display
P110
Energy indicator
P111
Energy indicator range
A6V11545892_en--_a
2 K
0.5...6 K
1 K
0.5...6 K
2 K
0.5...6 K
2 K
0.5...5 K
2 K
0.5...5 K
45 min
0...120 min
16 °C (61 °F)
5 °C...P060-2 K (41 °F...P060-2 K)
28 °C (82 °F)
P059+2 K...40 °C (P059+2 K...104 °F)
OFF
OFF, 0 °C...P064 (32 °F...P064)
OFF
OFF, P063...50 °C (P063...122 °F)
8 °C (46 °F)
OFF, 5 °C...P101; (41 °F...P101)
OFF
OFF, P100...40 °C; (P100...104 °F)
OFF
OFF, 1...360 min
OFF
0 = Disabled (OFF)
1 = Enabled (ON)
2 = Enabled (ON), excluded Window
contact
3 = Enabled (ON), excluded presence
detector (include hotel presence)
1
1 = Absolute setpoints
2 = Relative setpoints
1
OFF = Disabled
1 = Green and Red dimmed out
2 = Green dimmed out / Red fixed
3 = Green and Red fixed
2 K
0...10 K
Functions
4
Control parameters
P201,
P203,
P204
P001,
P150,
P153,
P155
P001,
P150,
P153,
P155
P150,
P153,
P155
P150,
P153,
P155
P002
113 | 150