Setting/Downloading Parameter Via Tool - Siemens RDG200KN Basic Documentation

Room thermostats with knx communications
Hide thumbs Also See for RDG200KN:
Table of Contents

Advertisement

4.15.2 Setting/downloading parameter via tool

ACS
OZW772 Web server
ETS
Connecting a KNX tool
A6V11545892_en--_a
The control parameters can be adjusted via bus either by parameter download
during commissioning or during normal operation with a tool like ACS.
With the ACS tool, the parameters can be changed...
During commissioning via parameter download (all parameters)
During operation via Popcard (most parameters)
Most parameters can be changed during operations using the OZW772 web
server.
ETS is an engineering tool used to fully commission RDG2..KN KNX room
thermostats. Device address, application, and control parameters can be defined
and downloaded via ETS.
Note: If users abort operation during commissioning, full commissioning cannot be
restarted until the device reboots. Before rebooting, only the application can be
downloaded.
Connecting a KNX commissioning/operating tool to the RDG2..KN is described in
Commissioning.