Siemens RDG200KN Basic Documentation page 103

Room thermostats with knx communications
Hide thumbs Also See for RDG200KN:
Table of Contents

Advertisement

Obj
Object name
21
Room temp: [P19]
Temperature
Economy heating
setpoint
Communication object adjusts the Economy heating setpoint used
by the thermostat (see Setting and adjusting setpoints [➙ 34]). It
directly changes the value of the local parameter "Economy
heating setpoint" P019.
S-Mode object needs to be enabled by setting Room temperature:
Economy Setpoint to as group object in ETS.
The Economy heating setpoint is stored in EEPROM. The service
life of the EEPROM depends on the number of write cycles. Never
write this communication object cyclically.
22
Room temp: [P20]
Temperature
Economy cooling
setpoint
Communication object adjusts the Economy cooling setpoint used
by the thermostat (see Setting and adjusting setpoints [➙ 34]). It
directly changes the value of the local parameter "Economy
cooling setpoint" P020.
S-Mode object needs to be enabled by setting Room temperature:
Economy Setpoint to as group object in ETS.
The Economy cooling setpoint is stored in EEPROM. The service
life of the EEPROM depends on the number of write cycles. Never
write this communication object cyclically.
23
Room operating
Open
mode: Window
Closed
contact
The RDG2..KN operating mode is set to Protection if value "1"
(open) is received and switches back to the previous mode for
value "0" (closed). The "Window contact" is sent e.g. by a KNX
switch and has the same effect as local window contact X1, X2 or
U1 (P150, P153 or P155). Only one input source required either a
local input X1/X2/U1 or KNX bus.
24
Room operating
Occupied
mode: Presence
Unoccupied
detector
Standard presence: The thermostat is set to Comfort mode if
value "1" (occupied) is received. It switches back to previous
operating mode when the value is "0" (unoccupied).
"Presence detector" is sent via KNX. It has the same effect as the
local presence detector function on X1, X2, U1 (parameter P150,
P153, P155).
Only one input source must be used, either local input X1/X2/U1
or KNX bus.
25
Room temp:
Temperature
Comfort basic
setpoint
If function "Temporary comfort setpoint" is enabled via P103, once
operating mode is changed, the setpoint adjustments made by the
user and via communication object 25 are dismissed. Then the
thermostat is reset to the Comfort basic setpoint.
Note: Setpoints that have been changed via the local HMI may be
overwritten during a system startup from a central master
controller, e.g., RMB795B.
The Comfort basic setpoint is stored in EEPROM (see Setting and
adjusting setpoints [➙ 34]). ➙ The service life of the EEPROM
depends on the number of write cycles. Never write this
communication object cyclically.
A6V11545892_en--_a
Function
Type/
Flags
length
9.001
CW
2 bytes
9.001
CW
2 bytes
1.019
CWU
1 bit
1.018
CWU
1 bit
9.001
CWU
2 bytes
Communication objects (S-Mode)
Obj
Object name
26
Room temp:
Temperature
Comfort setpoint
abs (receive)
Communication object shifts the setpoint (absolute) used by the
thermostat received via bus (see Setting and adjusting setpoints
[➙ 34]). The priority is same as local setpoint shift on the
thermostat. The last selected option is always used.
Note: The Comfort basic setpoint (object 25) will not be changed.
27
Room temp:
Temperature
Comfort setpoint
abs (send)
Sends the current Comfort absolute setpoint value used in the
RDG2..KN (see Setting and adjusting setpoints [➙ 34]).
28
Room temp:
Temperature
Current setpoint
Current setpoint, including shift, compensation, etc., used by the
thermostat for temperature control.
Setpoint
Temperature
29
cool set (receive)
setpoint setting
30
heat set (receive)
for 4 HVAC
modes
Receive a set of all cool / heat setpoints for all modes. (Comfort,
Pre-Comfort, Economy and Protection)
Depending on selected application, the relevant setpoint of only
heating / only cooling / heating and cooling will be stored
accordingly.
Setpoint
Temperature
31
cool set (send)
setpoint setting
32
heat set (send)
for 4 HVAC
modes
Send a set of cool / heat setpoints used in the device for all
modes. (Comfort, Economy and Protection)
Depending on selected application, the relevant setpoint of only
heating / only cooling / heating and cooling will be sent
accordingly.
33
Room
Temperature
temperature:
Comfort setpoint
rel (receive)
Communication object shifts the setpoint (relative) used by the
thermostat (see Setting and adjusting setpoints [➙ 34]). The
priority is same as local setpoint shift on the thermostat. The last
selected option is always used.
Note: The Comfort basic setpoint (object 25) will not be changed.
34
Room
Temperature
temperature:
Comfort setpoint
rel (send)
Sends the current Comfort relative setpoint value used in the
RDG2..KN (see Setting and adjusting setpoints [➙ 34]).
Note: The Comfort basic setpoint (object 25) will not be changed.
Functions
4
Function
Type/
Flags
length
9.001
CWU
2 bytes
9.001
CRT
2 bytes
9.001
CRT
2 bytes
275.100
CW
8 bytes
275.100
CR
8 bytes
9.002
CWU
2 bytes
9.002
CRT
2 bytes
103 | 150