Siemens RDG200KN Basic Documentation page 18

Room thermostats with knx communications
Hide thumbs Also See for RDG200KN:
Table of Contents

Advertisement

Notes
3
Commissioning
Control sequence
Calibrate sensor
Setpoint and range
limitation
Programming mode
Assign KNX device
address
Assign KNX group
address
KNX serial number
18 | 150
ACS and ETS require an interface:
KNX interface (e.g. Siemens N148...)
OCI702 USB-KNX interface
Set the control sequence via parameter P001 depending on the application.
Factory setting:
Application
2-pipe and chilled/heated ceiling, and 2-stage
4-pipe, chilled ceiling and radiator,
6-port ball valve applications
Recalibrate the temperature sensor, if the room temperature displayed on the
thermostat does not match the room temperature measured (after min. 1 hour of
operation). To do this, change parameter P006.
We recommended to review the setpoints and setpoint ranges (P011,
P013...P016, P019, P020) and change them as needed to achieve maximum
comfort and save energy.
The programming mode helps identify the thermostat in the KNX network during
commissioning.
Touch both the left and right buttons simultaneously for 6 seconds to activate
programming mode, indicated on the display by PROG.
Programming mode remains active until thermostat identification is complete.
Assign device address (P900) via HMI, ACS, ETS or Siemens smartphone
application PCT Go for Android.
Set the device address to 255 to deactivate the communication (no exchange of
process data).
Use ETS to assign the KNX group addresses of the thermostat's communication
objects.
Each device has a unique KNX serial number on the rear.
An additional sticker with the same KNX serial number is enclosed in the package.
This sticker is intended for documentation purposes of installers.
Factory setting P001
1 = Cooling only
4 = Heating and cooling
A6V11545892_en--_a