Example 3
A6V11545892_en--_a
Application for "Window contact", "Presence detector" and "Central time schedule"
In Room 3, the time schedule is between 13:00 and 17:00.
In the morning, as soon as presence is detected, the operating mode switches
to Comfort (1)
The users open the window briefly and the operating mode switches to
Protection (2)
In the afternoon, the central time schedule sets Comfort mode from 13:00 to
17:00 (3)
After 17:00, the room is still occupied, and the operating mode remains in
Comfort (occupancy via presence detector) (4)
The users open the window and exit the room for a short time. The operating
mode switches to Protection as long as the window is open (5)
As soon as the room is unoccupied, the thermostat switches to Economy (6)
After this time, occupancy detected by the presence detector has no effect, and
the central time schedule sets the thermostat to Protection (7)