Connection
6
Application examples
Example 2:
Swap and fan in the 2
nd
stage
138 | 150
2-pipe and 2-stage application with radiant heating/cooling panels, the fan only
operates with the fan coil unit:
●
Heating sequence: 1
●
Cooling sequence: 1
Commissioning
●
Fan
●
Valve
●
Valve
●
Swap
See Technical data [➙ 140] for min. and
max. ratings
panel and 2
fan coil unit
st
nd
fan coil unit and 2
panel
st
nd
P350 = 6 (Cooling
and 2
stage heating)
nd
P201 = 5 (panel)
P203 = 5 (fan coil
unit)
P254 = 1
Outputs used
●
M1
DC 0...10 V fan
(2
stage)
nd
●
V1
DC valve panel
●
V2
DC valve fan coil
unit
RDG260KN
A6V11545892_en--_a