Technical data
7
142 | 150
Multifunctional inputs
Temperature range
Temperature sensor input
Type
Temperature range
Digital input
Operating action
Contact sensing
Insulation against mains
KNX bus
Interface type
Bus current
Bus topology: See KNX manual ("Reference documentation")
Operational data
Switching differential, adjustable
Heating mode
Cooling mode
P-band Xp
Heating mode
Cooling mode
Setpoint setting and setpoint range
Comfort mode
Economy mode
Protection mode
Multifunctional inputs X1/X2/U1
Input X1 default value
Input X2 default value
Input U1 default value
Built-in room temperature sensor
Measuring range
Accuracy at 25 °C
Temperature calibration range
Built-in humidity sensor
Measuring range
Accuracy (after calibration via P007)
-20...70 °C
LG-Ni1000
-40...70 °C
Selectable (NO/NC)
DC 0...5 V, max. 5 mA
SELV
KNX, TP Uart 2 (electrically isolated)
5 mA
(P051) 1 K (0.5...6 K)
(P053) 1 K (0.5...6 K)
(P050) 2 K (0.5...6 K)
(P052) 1 K (0.5...6 K)
(P011) 21 °C (5...40 °C)
(P019-P020) 15 °C/30 °C (OFF, 5...40 °C)
(P100-P101) 8 °C/OFF (OFF, 5...40 °C)
Selectable (0...25)
(P150) 1 (external temperature sensor, room or
return air)
(P153) 0 (no function)
(P155) 3 (window contact)
0...49 °C
< ±0.5 K
±3 K
10...90 %
< 5 %