6.3.3 Swap function and/or fan in the 2nd stage

Example 1:
Fan in the 2
stage
nd
A6V11545892_en--_a
2-pipe fan coil application for floor heating/cooling (2-stage heating/cooling), fan
runs only in the 2
stage:
nd
Commissioning
Fan
Valve
Valve
See Technical data [➙ 140] for min. and
max. ratings
Outputs used
P350 = 4 (2
stage)
nd
P201 = 5 (floor)
P203 = 5 (fan coil
unit)
Connection
Application examples
M1
DC 0...10 V fan
V1
DC valve floor
V2
DC valve fan coil
units
RDG260KN