 Error table
Error description
IMPERMISSIBLE_PARAMETER_NUMBER
FAULTY_SUBINDEX
NO_ARRAY
PARAMETER_ADDRESS_IMPERMISSIBLE
ILLEGAL_FORMAT
AXIS_DO_NONEXISTENT
SERVICE_NOT_SUPPORTED
MULTI_PARAMETER_ACCESS_NOT_SUPPORTED
 Starting/stopping the motor
While inverter is in operation state it can be stopped in different ways using control word 1 (STW1).
Quick stop results in the motor decelerating to a stop. This stop is achieved by disabling "no quick stop" bit (STW1 bit 2). After
quick stop inverter transfers to "Switching ON inhibited" state.
Coast stop results in cutting power from motor and letting it coast to stop. This stop is achieved by disabling "no coast stop" bit
(STW1 bit 1). After coast stop inverter transfers to "Switching ON inhibited" state.
Disabling "ON" bit (STW1 bit 0) will result in motor decelerating to stop according to Pr.8. Inverter transfers to "Ready for
Switching ON" state.
Disabling "Enable Operation" bit (STW1 bit 3) will result in motor coasting to stop, after stopping inverter transfers to "Switched
ON" state. After quick stop inverter transfers to "Switching ON inhibited" state.