Mitsubishi Electric MELSEC iQ-R Series User Manual page 489

Serial communication module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Error code
Error
(hexadecima
l)
7FDEH
Modem function
error
7FDFH
Modem function
error
7FE0H
Modem function
error
7FE1H
Modem function
error
7FE2H
Modem function
error
7FE3H
Modem function
error
7FE4H
Modern function
error
7FE5H
Modem function
error
7FE6H
Remote password
error
Description
Signal
name
• Connection to the modem/
CHn
TA failed, or a modem/TA
ERR.
is not connected.
• The modem connection
CHn
channel No. has not been
ERR.
set.
• The designated value for
modem connection
channel is incorrect.
• The user frame No.
CHn
designation is incorrect.
ERR.
• The output start pointer
designation is incorrect.
• The output frame No.
CHn
designation is incorrect.
ERR.
• The registration data byte
CHn
count designation is
ERR.
incorrect.
• The data for connection of
CHn
the number specified in
ERR.
the data No. for
connection designation is
incorrect.
• The no-communication
CHn
interval time designation
ERR.
is incorrect.
• Remote passwords do not
match.
Corrective action
Protocol
MC
• Check if the modem/TA has
any failure by referring to the
instruction manual for the
modem/TA.
• Connect the modem/TA to
C24.
• Check the connection cable
by referring to the instruction
manual for the modem/TA.
• Check for any abnormality
according to the following
procedure.
(Page 490 Corrective
actions for system error)
• Set the modem connection
CH specification to 1 or 2.
• Set the modem connection
CH specification to 1 or 2.
• Review the user frame No.
• Designate the registered user
frame No.
• Register the designated data
for initialization.
• Set the output start pointer
designation to 1 to 100.
• Designate the position (n-th)
to which the number of data
for initialization is designated.
• Designate the number of data
for initialization to the
designated position (n-th).
• Designate the registered
number of data for
initialization to the range of the
designated output quantity
starting from the position of
the output start pointer
designation.
• Set the data for initialization to
1 to 78.
• Set the data for connection to
80.
• Review the data for
connection.
• Set the no-communication
interval time designation to 0
to 120.
• Review the remote password
and restart data
communications.
Nonpr
Bidire
Prede
ocedu
ctiona
fined
ral
l
27 TROUBLESHOOTING