Error code
Error
(hexadecima
l)
7F20H
ASCIIBIN
conversion error
7F21H
Receive header
area error
7F22H
Command error
7F23H
MC protocol
message error
7F24H
Sum check error
Description
Signal
name
• When the nonprocedural
PRO
or bidirectional protocol is
used, an ASCII code that
cannot be converted to
binary code was received.
• When the nonprocedural
or bidirectional protocol is
used, an odd number of
bytes of data was
received during data
communications using
ASCII  BIN conversion.
• When data is received by
PRO
Conversion Variable of the
predefined protocol
function, the data
corresponding to the
Conversion Variable
cannot be converted to
binary numbers.
• When data is received by
a Check code (ASCII
hexadecimal or ASCII
decimal) of the predefined
protocol function, the data
corresponding to the
check code cannot be
converted to binary
numbers.
• The command (frame)
PRO
part designation has an
error.
• An ASCII code that
cannot be converted to
binary code was received.
• A nonexistent command,
PRO
subcommand, or device
was designated.
• The remote password
length is incorrect.
• There is no data (ETX,
PRO
CR-LF, etc.) following the
character area, or the
designation was incorrect.
• The sum check code
P/S
calculated does not match
the sum check code
received.
• The horizontal parity code
calculated does not match
the horizontal parity code
received.
• The calculated check
code does not match the
received check code.
Corrective action
Protocol
MC
• Check and correct the
transmission message from
the target device and restart
data communications.
• When the nonprocedural or
bidirectional protocol is used
and data is communicated
using ASCII  BIN
conversion, be sure to send
data in units of even bytes.
■If the predefined protocol was
edited, check if the following
values match the packet format
of the target device:
• Conversion, sign character,
number of decimals, delimiter,
number of digit for conversion
variable
• Code type and data length of
check code
• Check and correct the
transmission message from
the target device and restart
data communications.
• Check and correct the
transmission message from
the target device and restart
data communications.
• Check and correct the
transmission message from
the target device and restart
data communications.
• Review the sum check code of
the target device.
• Review the horizontal parity
code of the target device.
• Review CRC-16 of the target
device.
■If the predefined protocol was
edited, check if the following
values match the packet format
of the target device:
• Processing method or code
type of the check code
• Data length
• Data flow
• Complement calculation
• Calculating range