When the transmission control is performed with "Send data" set to "Enable" and "Receive data" set to
"Enable", C24 performs message transmission and message reception processing as described below.
(Page 239 Control Contents of DC Code Control)
During message transmission processing, time check by timer 1 (response monitoring time) is performed.
● Message transmission (-1 in the figure)
• When C24 receives a transmission terminate request (receiving DC3/DR(DSR) signal OFF) from the target
device during message transmission, C24 terminates data transmission.
• When the C24 receives a reception available signal (receiving DC1/DR(DSR) signal ON), C24 restarts data
transmission.
● Message reception
• If C24 cannot send a response message to the target device in response to message reception because the
target device issued a transmission terminate request (receiving DC3/DR(DSR) signal OFF), C24 transmits
the response message after it's in the data transmission available state (receiving DC1/DR(DSR) signal
ON).
4 DATA COMMUNICATION USING BIDIRECTIONAL PROTOCOL
106
4.3 Processing when Simultaneous Transmission is Performed during Full-Duplex Communications