Mitsubishi Electric MELSEC iQ-R Series User Manual page 292

Serial communication module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Examples of registering a receive user frame
The following are examples of pre-registering a receive user frame on the CH1 side with Engineering tool.
■When the start frame is specified
In the example, the following three combinations are registered for the receive user frame.
• Setting conditions
User frame
1st
(Start frame + Final frame)
combination
2nd
(Start frame only)
combination
3rd
(Start frame only)
combination
• Setting value
Setting item
Receive end data quantity designation
Receive end code designation
User frame specification for receiving
User frame use enable/disable designation
User frame specification for receiving
Start frame No. designation
User frame specification for receiving
Final frame No. designation
User frame receiving method
designation
Method 1 dedicated receive end data
quantity designation
15 DATA COMMUNICATIONS USING USER FRAMES
290
15.2 Data Reception
User frame receiving method
designation
Method 0
Method 1
Method 1
Setting value
1FFH
FFFFH
Use
1st
3E8H
2nd
3E9H
3rd
3EAH
4th
0H
1st
41DH
2nd
0H
3rd
0H
4th
0H
1st
Method 0
2nd
Method 1
3rd
Method 1
4th
Method 0
1st
0H
2nd
0H
3rd
2H
4th
0H
Method 1 dedicated receive
end data quantity
0H
2H
Remarks
For Method 0
Set to "No designation" for receive end code.
Always specify "Use".
0H: No designation
1H or higher: Designated
In this setting, only three combinations become valid.
The receive end data quantity becomes valid.
Method 1 dedicated receive end data quantity becomes valid.
For Method 1
Remarks
The receive end data
quantity becomes valid.
Method 1 dedicated
receive end data quantity
becomes valid.

Hide quick links: