Mitsubishi Electric MELSEC Q Series Reference Manual page 322

Q corresponding melsecnet/h network system
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

8
TROUBLESHOOTING
Error code
Interruption error due to loop switching
FD1C
during test
FD1D
System error
FD1E
Bus topology, test disabled error
FD20
Mode error
FD21
Hardware error (send interrupt error)
FD22
Hardware error (receive interrupt error)
FD23
Data comparison error
FD24
Retry over
FD25
Input port initial value check error
FD26
Light check forward side error
FD27
Light check reverse side error
FD28
RAM check error
FD29
ROM check error
FD2A
Timer function check error
FD2B
WDT function check error
FD31
Online test request error
FD32
System error
FD33
System error
FD35
Response wait timeout occurred
FD36
Action wait timeout occurred
FD37
Another online test being executed
FD38
Duplicate message error
Communication test request destination
FD39
error (host station)
Communication test request destination
FD3A
error (station to which the test cannot be
requested)
FE20
Received data error
FE21
ZNRD/ZNWR device range error
FE22
AnU request error
FE23
System error
FE24
System error
8 - 42
Table 8.1 Error code list (Continued)
Description
There is no need to take corrective measures because the system retries the
operation (do not switch the loop in the middle of the operation).
If the error frequently occurs, check the line and the wiring status.
The hardware of the network module is faulty.
Please consult your local Mitsubishi representative.
Conduct a test that can be executed in the bus topology.
Create new network parameters and perform Write to PLC.
If the error reoccurs, the hardware of the CPU or network module is faulty.
Please consult your local Mitsubishi representative.
The cable was disconnected during the online test.
Reconnect the cable, and continue the online test.
Check for faulty cables, faulty hardware, incorrect wiring, and absence of
terminating resistor (in the case of the bus). In addition, check whether the
same station number has been set for two or more stations or whether two or
more control stations exist.
The hardware of the network module is faulty.
Please consult your local Mitsubishi representative.
There is a problem with the cable.
Connect a proper cable, and perform an online test.
The hardware of the network module is faulty.
Please consult your local Mitsubishi representative.
Wait until a currently-executed online test ends, and execute another online
test.
The hardware of the network module is faulty.
Please consult your local Mitsubishi representative.
Retry after a little while.
Check the status of the relevant station and of the line.
Change the test request destination.
A station to which a test request is not available was specified.
GX Developer
C
N
C
N
C
Review the routing parameters, or replace the relay CPU module with the AnU
or QnA CPU module compatible with the MELECNET/10.
Review the range of the device to be accessed with the ZNRD/ZNWR
instructions to the ACPU.
Check if access to other station is made from GX Developer with a project of a
different CPU type.
The hardware of the source module starting dedicated instructions and MC
protocol is faulty.
Please consult your local Mitsubishi representative.
Confirm the status of the target station and relay station CPU modules.
Alternatively, change the CPU module concerned.
Corrective action
C
:CPU module
N
:Network module
:Communication request
disabled station
N N
C
N
C
N N
C
MELSEC-Q
N
8 - 42