Mitsubishi Electric MELSEC Q Series Reference Manual page 150

Q corresponding melsecnet/h network system
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

4
SETTING AND PROCEDURE BEFORE OPERATION
CPU
module
CPU
module
4 - 30
(2) Starting the test
(a)
High Performance model QCPU, Process CPU, and Redundant CPU
Set the RUN/STOP switch of the CPU module to the STOP position. When
resetting the CPU module, use the RESET/L.CLR switch.
Center
3
4
5
STOP
RUN
RESET L.CLR
(b)
Universal model QCPU
Reset with the RESET/STOP/RUN switch.
Hold the switch in the RESET position until the ERR. LED starts flashing,
and release it after the LED turns off.
STOP
RESET
RUN
STOP
POINT
To execute the forward loop/reverse loop test, connect the cable correctly to OUT
and IN.
Also, do not connect or disconnect the cable during execution of the test. (Doing so
will result in test failure.)
RESET
3
4
5
STOP
RUN
RESET L.CLR
The ERR. LED flickers.
When it goes off, release
Move to RESET.
the switch.
RESET
RUN
STOP
MELSEC-Q
Center
3
4
5
STOP
RUN
RESET L.CLR
RESET
RUN
STOP
4 - 30