8
TROUBLESHOOTING
Error code
Corresponding station error
F111
(Baton pass to the corresponding station
not executed)
F112
Faulty loop status
Send failure
F113
(Baton pass to the host station not
executed)
F114
Send failure
F115
Improper function code
F116
Delayed online test processing
F117
Send failure
F118
Send failure (baton regeneration)
Send failure
F11A
(multiplex transmission stopped)
F11B
Being disconnected
F11C
System error
8 - 36
Table 8.1 Error code list (Continued)
Description
Review the status of the corresponding station and the parameter and switch
settings (to see if there is a parameter error and the corresponding station is the
control station and properly set).
Confirm the power supply status of the corresponding station (to see if it is
repeatedly turned on and off).
Check for faulty cables, faulty hardware, incorrect cable wiring, and absence of
terminating resistor (in the case of the bus). In addition, check whether the
same station number has been set for two or more stations or whether two or
more control stations or remote master stations exist.
The setup confirmation test and loop test of network diagnosis are effective.
Check for faulty cables, faulty hardware, and incorrect wiring. In addition, check
whether the same station number has been set for two or more stations or
whether two or more control stations or remote master stations exist.
Confirm the power supply status of each module (to see if it is repeatedly
turned on and off).
Confirm whether network modules in MESLECNET/H and MELSECNET/10
modes exist together (confirm the control station type).
Retry after a little while.
If the error reoccurs as a result of a retry, check for faulty cables, faulty
hardware, incorrect cable wiring, and absence of terminating resistor (in the
case of the bus). In addition, check whether the same station number has been
set for two or more stations or whether two or more control stations or remote
master stations exist.
Wait until SB0047 (baton pass status) and SB0049 (data link status) are
recovered.
Retry after a little while.
If the error reoccurs as a result of a retry, check for faulty cables, faulty
hardware, incorrect cable wiring, and absence of terminating resistor (in the
case of the bus). In addition, check whether the same station number has been
set for two or more stations or whether two or more control stations or remote
master stations exist.
Wait until SB0047 (baton pass status) and SB0049 (data link status) are
recovered.
Check for faulty cables, faulty hardware, and incorrect wiring. In addition, check
whether the same station number has been set for two or more stations or
whether two or more control stations or remote master stations exist.
Check for faulty cables, hardware failure, noise, incorrect wiring, and absence
of terminating resistors (when a bus is used).
Wait until SB0047 (baton pass status)/SB0049 (data link status) is turned off
(normal).
Wait for a while and execute again.
Review the parameter and switch settings (to see if there is a parameter error
and the corresponding station is the control station or remote master station
and properly set).
Check for faulty cables, faulty hardware, and incorrect wiring. In addition, check
whether the same station number has been set for two or more stations or
whether two or more control stations or remote master stations exist.
The hardware of the network module is faulty.
Please consult your local Mitsubishi representative.