Mitsubishi Electric MELSEC Q Series Reference Manual page 240

Q corresponding melsecnet/h network system
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

7
APPLICATION FUNCTIONS
Write command
Z.REMTO
Write command
ZP.REMTO
Jn
Target network No.
(n1)
Channel number
(n2)
Target number
Start address input/output number for target intelligent function module
The upper 3 digits of the 4-digit expression designates the start address input/output
(n3)
number for the intelligent function module mounted to the remote I/O station that is to be
the target.
Write buffer memory start address
(n4)
Designates the start address of the buffer memory for the write destination intelligent
function module.
Write data storage start address device (Host)
(D1)
Designates the host start address device for storing the written data.
(n5)
Number of write data points (word modules)
Write completion device (Host)
Designates the host device to be set to 1 scan on by the write completion.
(D2)
(D2) · · · · · · OFF: Not completed ON: Completed
(D2) + 1 · · · OFF: Normal
1: Bit device ........................................... X, Y, M, L, F, V, B
2: Word device ...................................... T, C, D, W, ST, R, ZR
3: Word device bit designation ............. Word device.bit number
7 - 4
2)
Z(P).REMTO
(Network No. designation)
"Jn"
n1
n2
"Jn"
n1
n2
: If the originating station is a Universal model QCPU, " "(double quotation) for the
first argument can be omitted.
Description of setting
ON: Abnormal
n3
n4
D1
n5
n3
n4
D1
n5
MELSEC-Q
Z: Executed when on
D2
ZP: Executed when rising
D2
Setting range
1 to 239
1 to 8
2
Word device
1 to 64
2
Word device
0 to FE
H
2
Word device
Constant (K, H)
2
Word device
2
Word device
1 to 960
2
Word device
1
Bit device
Word device bit designation
3
7 - 4