TZIDC, TZIDC-110, TZIDC-120 DIGITAL POSITIONER | CI/TZIDC/110/120-EN REV. E

Setting the bus address

1. Switching to the configuration level:
Press and hold down and  simultaneously,
additionally quickly press and release ENTER,
Wait for the countdown to go from 3 to 0,
Release and .
The following is now shown in the display:
M10906i
2. Switch to parameter group 1.5:
Press and hold down MODE and ENTER simultaneously,
additionally, press  and .
The following is now shown in the display:
%
conf
Release MODE.
The following is now shown in the display:
conf
3. Setting the bus address:
Press or  to set the correct value,
Press and hold down ENTER until the countdown goes
from 3 to 0.
Release ENTER.
The new bus address is saved.
4. Switch to parameter 1.6 (return to operating level) and save
the new setting:
Press and hold down MODE,
additionally quickly press  2 times,
The following is now shown in the display:
%
co nf
Release MODE,
Quickly press and release  to select NV_SAVE,
Press and hold down ENTER until the countdown goes
from 3 to 0.
The new parameter setting is saved and the positioner
automatically returns to the operating level. It continues in the
operating mode that was active prior to the configuration level
being called up.

Request information

When the device is in bus operation, the information listed below
can be called up.
Press the following control buttons to access this information:
Control buttons
Cyclic communication:
Acyclic communication:
Displays the bus address and operating mode.
Displays the software revision.
Enter
Action
Set point in % and the set point status
is displayed.
Displays the communication status.
45