Operating Modes; Jumper Configuration; Standard Automatic Adjustment; Standard Automatic Adjustment For Linear Actuators - ABB TZIDC Commissioning Instruction

Digital positioner
Hide thumbs Also See for TZIDC:
Table of Contents

Advertisement

46
TZIDC, TZIDC-110, TZIDC-120 DIGITAL POSITIONER | CI/TZIDC/110/120-EN REV. E
... 8 Commissioning
... TZIDC-110 / TZIDC-120

Operating modes

Selection from the operating level:
1. Press and hold down MODE.
2. Also press and release  rapidly as often as required. The
selected operating mode is displayed.
3. Release MODE.
The position is displayed in % or as a rotation angle.
Operating mode
Mode indicator
1.1
Positioning with fixed set
point.
Adjust set point by using
 or .
1.2
Manual adjustment * in
the operating range.
Adjust with  or  **
1.3
Manual adjustment *
within the sensor range.
Adjust with  or  **
*
Positioning not active.
** For high-speed mode, press  and  simultaneously.

Jumper configuration

Only on TZIDC-120
There are two jumpers on the mainboard that can be used to
activate or block simulation mode and write access.
Set the jumpers as shown below:
Figure 24: TZIDC-120 jumpers
Jumper
Number
1
A
B
2
A
B
*
Default setting (in accordance with Fieldbus Foundation standard)
Position indicator
M10906b
Function
Simulation blocked*
Simulation enabled
Write access blocked
Write access activated*

Standard automatic adjustment

Note
Standard Auto Adjust does not always result in optimum control
conditions.

Standard automatic adjustment for linear actuators*

1. MODE Press and hold until ADJ_LIN is displayed.
2. MODE Press and hold until the countdown ends.
3. Release MODE; this starts Autoadjust.

Standard automatic adjustment for rotary actuators*

1. ENTER Press and hold until ADJ_ROT is displayed.
2. ENTER Press and hold until the countdown ends.
3. Release ENTER; this starts Autoadjust.
If Autoadjust is successful, the parameters will be stored
automatically and the positioner will revert to operating
mode 1.1.
If an error occurs during Autoadjust, the process will be
terminated with an error message.
Perform the following steps if an error occurs:
1. Press and hold down operating button  or  for
approximately three seconds.
The unit will switch to the operating level, mode 1.3 (manual
adjustment within the measuring range).
2. Check mechanical mounting in accordance with Mechanical
mounting on page 27 and repeat the standard automatic
adjustment.
*
The zero position is determined automatically and saved during standard
automatic adjustment, counter-clockwise (CTCLOCKW) for linear actuators
and clockwise (CLOCKW) for rotary actuators.