Acknowledging A Fault When Esm/Fire Mode Is First Enabled; Advanced Settings; Esm/Fire Mode Control Words For The Sed2 - Siemens SED2 Application Manual

Variable speed drive fire mode
Hide thumbs Also See for SED2:
Table of Contents

Advertisement

Note
Siemens
Building Technologies
The following parameters will need to be considered for ESM even if P1210 is dif-
ferent to setting 6 in normal operation mode:
P1212 (time to first restart)
P1213 (restart time increment) = 30 seconds default
If P1210 = any setting other than 6 when ESM is not activated (normal operation mode),
when ESM is active the setting of 6 will not be visible as this will occur internally.
6.6.5
Acknowledging a fault when ESM/Fire Mode is first en-
abled
If a fault is active prior to ESM/Fire Mode being enabled, when ESM is enabled the
SED2 will acknowledge, restart and ignore all 'soft faults' and attempt to acknowl-
edge and restart any 'hard faults'. If a hard fault is still present, then the SED2 will
trip and attempt again indefinitely or until the SED2 is destroyed.
6.7

Advanced settings

6.7.1

ESM/Fire Mode Control Words for the SED2

P1271 has introduced two new control words that will take priority once ESM has
been enabled. These control words have no effect on standard
SED2.
P1271 in000
Bit00 ON/OFF1
Bit01 OFF2: Electrical stop
Bit02 OFF3: Fast stop
Bit03 Pulse enabled
Bit04 RFG enabled
Bit05 RFG start
Bit06 Setpoint enabled
Bit07 Fault acknowledge
Bit08 JOG right
Bit09 JOG left
Bit10 Not used
Bit11 Reverse (setpoint inversion)
Bit13 Motor potentiometer MOP up
Bit14 Motor potentiometer MOP down
Bit15 CDS Bit 0 (Hand/Auto)
P1271 in 001
Bit00 Fixed frequency Bit 0
Bit01 Fixed frequency Bit 1
Bit02 Fixed frequency Bit 2
Bit03 Fixed frequency Bit 3
Bit04 Not Used
Bit05 Not Used
Bit08 PID enabled
Bit09 DC brake enabled
Bit11 Droop enabled
Bit12 PID disabled
Bit13 External fault 1
Bit15 Not Used
bit 15 ............. 12 ................ 08
bit 07 ............ 04 ..... 02 01 00
Application Guide «Fire Mode»
Essential Service Mode (in-depth information)
= 30 seconds default
ESM Control Word 1
Ignored (drive always runs)
Always set (cannot be changed)
Always set (cannot be changed)
Always set (cannot be changed)
Always set (cannot be changed)
Always set (cannot be changed)
Always set (cannot be changed)
Always set (cannot be changed)
Selectable
Selectable
Ignored
Selectable
Selectable
Selectable
Forces Auto Mode (cannot be changed)
ESM Control Word 2
Selectable
Selectable
Selectable
Selectable
Ignored
Ignored
Selectable
Selectable (not generally used in HVAC functions)
Selectable (not generally used in HVAC functions)
Selectable
Ignored
Ignored
operation of the
1a
41 / 44
CM1A5192en_01
23.10.2007