Application example of
ESM
Siemens
Building Technologies
Once ESM is activated, "ES" is displayed on the SED2 BOP (Basic operating
Panel). ESM activation can also be assigned to one of the relays of the SED2.
The SED2 firmware offers ESM as a standard feature which can be enabled via a
parameter and also appropriately parameterized. We envisage a number of typical
applications for the ESM function. The following example shows a typical SED2
application in a shopping mall, including ESM:
L1
L2
L3
N
PE
Alarm Control Panel
• Several air handling plants are installed in a shopping center, using several
SED2 for the supply and extract air fans
• In normal operation, the Desigo system delivers the switch-on command and
setpoint to the VSD via bus
• If the fire alarm center activates ESM, the SED2 will start to operate with the
maximum speed at 50 Hz and suppresses the protective functions and error
messages as described above
• The plant will switch to overpressure operation in order to keep the rooms free
from smoke
Application Guide «Fire Mode»
Introduction
F1
F1
F1
L1
L2
L3
PE
1
DC 10V
12
2
DC 0V
AOUT1
13
4
26
3
AIN1
AOUT2
2
27
SED2
11
20
10
AIN2
DOUT1
21
2
22
23
28
DC 0V
DOUT2
DC 24V
24
9
25
DIN1
5
6
DIN2
7
DIN3
8
DIN4
16
DIN5
29
17
DIN6
RS-485
30
14
PTC
PTC
15
U
V
W
PE
M
Desigo PX
PTE-
SED2
13 / 44
CM1A5192en_01
23.10.2007

Advertisement

Table of Contents
loading

Table of Contents