Siemens SED2 Application Manual page 36

Variable speed drive fire mode
Hide thumbs Also See for SED2:
Table of Contents

Advertisement

36 / 44
Siemens
Building Technologies
Example 2
If you use DIN1 as ON/OFF1 (setting 1 = default) and DIN2 as ON reverse/OFF1
(setting 2) and in addition the ESM is set to reverse the behaviour of the SED2 is
as follows:
DIN1
DIN4
(ON/OFF1)
(ON reverse/OFF1
0
0
0
0
1
1
1
1
* Depending on which command is given first (DIN1 or DIN4).
If the digital inputs 2 (ESM) and 4 (Reverse) are active simultaneously the SED2
will run in normal direction. In this case the reverse signals cancel each other out.
Application Guide «Fire Mode»
Essential Service Mode (in-depth information)
DIN2
Motor Direction
(ESM)
0
0
Normal (Off)
0
1
Reverse
1
0
Reverse
1
1
Normal
0
0
Normal
0
1
Reverse
1
0
Normal or Reverse*
1
1
Normal
or Reverse*
CM1A5192en_01
23.10.2007