4.4.3

Parameter setting

Start with quick commissioning according the commissioning guide
CM1G5192.
Set P0700 to 5 (command source = Desigo = USS on COM link)
and P1000 to 53 (setpoint source = Desigo = USS on COM link).
It is very important to enter the right motor data!
Par. Nr.
Value
P0003
3
P0700
5
P0702(0)
99
P0702(1)
99
P1000
53
P1001
40
P1074(0)
722.1
P1074(1)
722.1
P1270(0)
722.1
P1270(1)
722.1
P1271(0)
P1271(1)
P2009(0)
1
P2010(0)
6
P2011(0)
1 (e.g.)
P2014(0)
0...65535
For further information please see also Chapter 5 – Commissioning Wizard for
Essential Service Mode.
4.4.4

Remarks

• The hand mode will be disabled automatically when ESM is active.
• The information "drive fault" and "drive running" is still available on the 2 relay
outputs.
On demand the information "ESM active" can be configured to a relay output.
• The fault F0072 (bus communication failure) will be ignored whilst ESM is active.
• In this example a DESIGO PX is used as the communication master but any
communication (FLN, P1, N2) could be used just as effectively.
Application Guide «Fire Mode»
Application Examples
Parameter function
User access level 3
Command source
Function of DIN2 in Auto mode
Function of DIN2 in Hand
mode
Setpoint source
Fixed frequency when ESM is
active
Disable Additional Setpoint in
Auto
Disable Additional Setpoint in
Hand
Activate ESM in Auto
Activate ESM in Hand
Activation of ESM control word
Enable FF in ESM mode
USS normalization COM-Link
USS baud rate COM-Link
USS address COM-Link
USS telegram off time
Function selection
Expert access
DESIGO (USS on
COM link)
BICO = free parame-
terization
BICO = free parame-
terization
DESIGO (USS on
COM link)
in Hz
Disable AI1
Disable AI1
DI2
DI2
press▼once;
will appear and ESM
control word is acti-
vated
press▲once
Enabled
9600 baud
Address range 1 to 31
0...65535ms (defines
a time after which a
fault message will be
generated (F0072 if
no telegram is re-
ceived via the USS
channels)
21 / 44
CM1A5192en_01
23.10.2007

Advertisement