6.1
Assigning the ESM function to a DIN
(Digital Input)
In accordance with the standards, all functions required of ESM can be assigned to
the same DIN and therefore eliminate the need for any additional inputs.
Our recommendation is to use DIN2 for ESM. However, any one of the DIN's can
be used (DIN1~DIN6)
L1
1
DC 10V
2
DC
4
3
AIN1
2
11
10
AIN 2
2
28
DC 0V
DC 24V
9
DIN 1
5
6
DIN 2
7
DIN 3
8
DIN 4
16
DIN 5
17
DIN 6
14
PTC
PTC
15
U
Fire Control Panel
Ensure DIN2 is OPEN during commissioning.
Parameter
Index
P0003
-
-
P0702
in 000
in001
P1270
in000
in001
6.2

Activating P1271 (ESM Control Word)

This should be carried out using the BOP (Basic Operating Panel)
Parameter
Index
P0003
-
-
P0702
in 000
in001
P1270
in000
in001
P1271
in000
Once P1271 has been activated, the ESM control word will take priority once the
DIN assigned to ESM/Fire Mode is enabled.
Application Guide «Fire Mode»
Essential Service Mode (in-depth information)
L2
L3
PE
12
0V
AOUT 1
13
26
AOUT 2
27
2
20
DOUT1
21
22
23
DOUT2
24
25
29
RS- 485
30
V
W
PE
Default
Set to Function and description
1
3
12
99
0
99
0.0
722.1
0.0
722.1
Default
Set to Function and description
1
3
12
99
Function of DIN2
0
99
0.0
722.1
Source command for ESM
0.0
722.1
bnnnr
Access Level
Set access level to Expert
Function of DIN2
Enable BICO parameterisation
Source command for ESM
Defines source as DIN2
Access Level
Set access level to Expert
Enable BICO parameterisation
Defines source as DIN2
ESM Control word 1
bnnnr
Press? ( once) and
will appear and
ESM control word is activated