Siemens
Building Technologies
6.5.3
PID Control in ESM/Fire Mode but
disabled in standard Mode
PID control in normal operation mode is switched off. P2200in000=0.0
All other PID parameters are set to suit application ESM/Fire Mode:
Parameter
Index
P0003
-
P1271
in001
P2200
in000
P2xxx
Display of P1271 in001 (ESM Control word 2) on the BOP
Alternatively, use EasyComm to set the correct bit.
6.5.4
PID Control disabled in ESM/Fire Mode
and Standard mode
Leave P2200 at factory default (0.0) and leave P1271 in000 bit08 inactive.
Application Guide «Fire Mode»
Essential Service Mode (in-depth information)
Default Set to Function and description
1
3
Access Level
Set access level to Expert
Activate bit 08 and de-activate bit12 to enable PID in ESM
0.0
0.0
PID Controller
leave setting at 0.0 to disable main PID controller
Configure PID related parameters
P2201~P23xx accordingly to application
39 / 44
CM1A5192en_01
23.10.2007