PID Control in Standard mode but disabled
in ESM/Fire Mode
Normal operation mode PID control should be configured as described in the Com-
missioning Guide.
P2200 in000/in001= 1.0 or whatever the source is.
P22xx~P23xx PID parameters set as per application ESM/Fire Mode:
Parameter
Index
P0003
-
P1271
in001
P2xxx
Display of P1271 in001 (ESM Control word 2) on the BOP
Alternatively, use EasyComm to set the correct bit.
Application Guide «Fire Mode»
Essential Service Mode (in-depth information)
Default Set to Function and description
1
3
Access Level
Set access level to Expert
ESM Control word1
Activate bit 12 and de-activate bi08 to disable PID in ESM
Configure PID related parameters
P2201~P23xx accordingly to application
CM1A5192en_01