Parameter Setting; Remarks - Siemens SED2 Application Manual

Variable speed drive fire mode
Hide thumbs Also See for SED2:
Table of Contents

Advertisement

Siemens
Building Technologies
4.6.3

Parameter setting

Start with quick commissioning according the commissioning guide
CM1G5192.
It is very important to enter the right motor data!
Par. Nr.
Value
P0003
3
P701 (0)
16
P0702(0)
26
P0702(1)
26
P0756(1)
1
P0757(1)
P0758(1)
P0759(1)
P0760(1)
P1000(0)
3
P1001
40
P1271(0)
P1271(1)
P2200(0)
1
P2201
50
P2253(0)
2224
P2280
1.2 (e.g.)
P2285
30s (e.g.)
P2306
1
2262
2272
2273
2280
bit 15 ............. 12 ................ 08
bit 07 ............ 04 ..... 02 01 00
For further information please see also Chapter 5 – Commissioning Wizard for
Essential Service .
4.6.4

Remarks

• The hand mode will be disabled automatically when ESM is active.
• The information "drive fault" and "drive running" is still available on the 2 relay
outputs.
On demand the information "ESM active" can be configured to a relay output.
Application Guide «Fire Mode»
Application Examples
Parameter function
User access level 3
Function of DIN2 in Auto mode
Function of DIN2 in Auto mode
Function of DIN2 in Hand
mode
Type of analog input 2
Scaling of AIN2: x1
Scaling of AIN2: y1
Scaling of AIN2: x2
Scaling of AIN2: y2
Setpoint source in Auto
Fixed frequency when ESM is
active
Activation of ESM control word
ESM control word
Enable PID controller
PID Setpoint of pressure con-
trol
Setpoint source
PID proportional gain
PID integral action time
PID acting direction
Current setpoint
Current feedback
PID error
PID output
With pressing ▲ this parameter counts
binary up.
To get the value
press ▲ for 12 s approx.
Function selection
Expert access
On + PID setpoint 1
ESM
ESM
DC 0...10V
(Default)
(Default)
(Default)
(Default)
FF
in Hz
press▲once
press▲until you get
(see
below)
Enabled
50%
Internal setpoint
Indirect
you'll have to
25 / 44
CM1A5192en_01
23.10.2007