Application Example 4; Description; Wiring Diagram - Siemens SED2 Application Manual

Variable speed drive fire mode
Hide thumbs Also See for SED2:
Table of Contents

Advertisement

20 / 44
Siemens
Building Technologies
4.4

Application Example 4

4.4.1

Description

• In normal operation the SED2 is controlled from the Desigo PX via bus commu-
nication using the PTE module.
• In case of fire the fire control panel signals this to the SED2, it is going in the
ESM mode and to a fixed frequency e.g. 40Hz.
4.4.2

Wiring diagram

L1
L2
L3
N
PE
Fire Control Panel
Application Guide «Fire Mode»
Application Examples
F1
F1
F1
L1
L2
L3
PE
1
DC 10V
12
2
DC 0V
AOUT1
13
4
26
3
AIN1
AOUT2
2
27
SED2
11
20
10
AIN2
DOUT1
21
2
22
23
28
DC 0V
DOUT2
DC 24V
24
9
25
DIN1
5
6
DIN2
7
DIN3
8
DIN4
16
DIN5
29
17
DIN6
RS-485
30
14
PTC
PTC
15
U
V
W
PE
M
Desigo PX
PTE-
SED2
CM1A5192en_01