ABB TZIDC Operating Instructions Manual page 38

Digital positioner
Table of Contents

Advertisement

38
TZIDC DIGITAL POSITIONER | OI/TZIDC-EN REV. B
... 8 Operation
... Parameter description HART®
Parameter Display
Function
P6._
MAN_ADJ
P6.0
MIN_VR
Min. valve range
P6.1
MAX_VR
Max. valve range
P6.2
ACTUATOR
Actuator type
P6.3
SPRNG_Y2
Spring action (Y2)
P6.4
DANG_DN
Dead angle close
P6.5
DANG_UP
Dead angle open
P6.6
BOLT_POS
Bolt position
P6.7
EXIT
Return
P7._
CTRL_PAR
P7.0
KP UP
KP value, up
P7.1
KP DN
KP value, down
P7.2
TV UP
TV value, up
P7.3
TV DN
TV value, down
P7.4
Y-OFS UP
Y offset, up
P7.5
Y-OFS DN
Y offset, down
P7.6
TOL_BAND
Tolerance band (zone)
P7.7
DEADBAND
Deadband
P7.8
DB_APPR
Deadband Approach
P7.9
TEST
Test
P7.10
DB_CALC
Deadband calculat.
P7.11
LEAK_SEN
Leakage sensivity
P7.12
CLOSE_UP
Pos. time out
P7.13
EXIT
Return
Operating range, min.
Operating range, max.
Actuator type
Spring action (Y2)
Dead angle 0 %
Dead angle 100%
Actuator position
Return to operating level
KP value (up)
KP value (down)
TV value (up)
TV value (down)
Y offset (up)
Y offset (down)
Tolerance band (zone)
Dead band
Dead-band approach
Test
Dead-band determination
Leakage sensitivity
Position monitoring
Return to operating level
Possible parameter setting
0.0 to 100.0
0.0 to 100.0
LINEAR, ROTARY
CLOCKWISE, CTCLOCKWISE
0.0 to 45.0
55.0 to 100.0
LEVER, STEM
Function
0.1 to 120.0
0.1 to 120.0
10 to 450
10 to 450
0.0 to 100.0
0.0 to 100.0
0.3 to 10.0
0.10 to 10.00
SLOW, MEDIUM, FAST
Function
ON, OFF
1 to 7200
0.0 to 100.0
Function
Unit
Factory setting
%
0
%
100
---
LINEAR
---
CTCLOCKWISE
%
0.0
%
100.0
---
LEVER
---
NV_SAVE
---
5.0
---
5.0
---
200
---
200
%
48.0
%
48.0
%
1.5
%
12:10 AM
---
INACTIVE
---
ON
S
30
%
30.0
---
NV_SAVE

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents