TZIDC Remote Sensor Electrical Connection

A Basic device
B Options
Figure 20: TZIDC Remote Sensor Electrical Connection
Change from one to two columns
Connections for inputs and outputs
Terminal
1 / 2 / 3
+51 / 52
+41 / 42
41 / 42 / 43
51 / 52 / 53
Note
The TZIDC Remote Sensor can be fitted either with proximity
switches or microswitches as limit switches. It is not possible to
combine both variants.

Electrical data for inputs and outputs

Note
When using the device in potentially explosive atmospheres,
note the additional connection data in Use in potentially
explosive atmospheres on page 5!
A
1
1
2
3
Function / comments
TZIDC control unit
Proximity switches Limit 1 (Option)
Proximity switches Limit 2 (Option)
Microswitches Limit 1 (Option)
Microswitches Limit 2 (Option)
B
2
+51 -52 +41 -42
41 42 43
1 Position sensor
2 Limit monitor with proximity switches (optional)
3 Limit monitor with microswitches (optional)
Analog input
Set point signal analog (two-wire technology)
Terminals
Nominal operating range
Split range configuration between
Maximum
Minimum
Starting at
Load voltage
Impedance at 20 mA
3
51 52 53
M10899
+11 / 12
4 to 20 mA
20 to 100 % of the nominal operating
range can be parameterized
9.7 V at 20 mA
23
50 mA
3.6 mA
3.8 mA
485