Parameter setting of the Safety CPU

Set Safety CPU parameters refer to the following.
Operating procedure
1.
Create a new project and set user authentication.
2.
Perform "Write User Data to PLC".
[Online]  [User Authentication]  [Write User Data to PLC]
3.
Perform "Log on to PLC".
[Online]  [User Authentication]  [Log on to PLC]
4.
Open the module configuration diagram and set system parameters.
"Navigation window"  "Module configuration diagram"
5.
Set device/label memory capacity.
[CPU Parameter]  "Memory/Device Setting"  "Device/Label Memory Area Setting"
6.
Set a safety cycle time.
[CPU parameter]  "Safety Function Setting"
For details on parameter setting method, refer to the following.
 MELSEC iQ-R CPU Module User's Manual (Startup)
 MELSEC iQ-R CPU Module User's Manual (Application)
User authentication settings
A Safety CPU project requires user authentication with a password. The "Add New User" window appears when a new project
is created. Enter required information into the window. Then, save the new project according to the direction given by the
window.
To read or write data with Safety CPU of safety remote I/O module, logging on to programmable controller is required. If user
information is not written on a programmable controller, select [Online]  [User Authentication]  [Write User Data to PLC] to
write appropriate user information. Select [Online]  [User Authentication]  [Log on to PLC] to logon to programmable
controller.
For details on user authentication setting method, refer to the following manual.
 GX Works3 Operating Manual
5 SAFETY APPLICATION CONFIGURATION EXAMPLES
5.2 System to Which Multiple Safety CPUs are Connected