■Wiring diagram and parameter settings
<CCIEF remote (1): SR_IO1>
Wire the light curtain and electromagnetic contactors to safety remote I/O module as follows. For details on the terminal block,
refer to the following.
 CC-Link IE Field Network Remote I/O Module (With Safety Functions) User's Manual
Optical transmitter
24VDC
0V
FG
Synchronization negative
Synchronization positive
Optical receiver
Synchronization positive
Synchronization negative
24VDC
Control output 1
FG
Control output 2
*1
0V
Light curtain
[1]
[3]
[2]
[4]
Above [1] to [4] are connected to the one with same numbers.
*1 Connect two points (PNP output) of the Type 4 light curtain control output to between input and COM.
*2 Use two electromagnetic contactors operatable by 24VDC and 0.5A.
*3 Connect normally closed contact of the electromagnetic contactor between the input terminal and test pulse terminal.
*4 Create a dual wiring.
5 SAFETY APPLICATION CONFIGURATION EXAMPLES
130
5.1 System Configured by a Safety CPU
24VDC
24VDC
24VDC
[1]
[2]
*4
[3]
[4]
Electromagnetic
*2*3
contactor
L3
24VDC
L2
L1
Electromagnetic
Muting lamp
*2*3
contactor
CCIEF remote (1)
NZ2GFSS2-32D
Network No.1
Station No.1
A1
+24V
A2
+24V
A3
24G
A4
24G
A5
FG
19
IO24V
20
IO24G
3
X2
4
X3
5
X4
6
X5
23
T0
24
T1
60
COM-
CCIEF remote (1)
NZ2EXSS2-8TE
Network No.1
Station No.1
19
IO24V
20
IO24G
1
Y0
2
COM-
3
Y1
4
COM-
5
Y2
6
COM-
Terminal block for power supply and FG (input)
A1
+24V
A2
+24V
A3
24G
A4
24G
A5
FG
Spring clamp terminal block (input)
Spring clamp terminal block (output)