Additional instructions for frame size R6

Cable terminals R+ and R-

Power cable conductors of sizes 95 to 185 mm
the cable terminals as follows:
• Undo the fastening screw of the terminal.
• Connect the conductor to the terminal.
• Screw the terminal to the original location.

Cable lug installations to R+ and R- screws

Cables of sizes 16 to 70 mm
cable lugs. Isolate the ends of the cable lugs with insulating tape or shrink tubing. To
meet UL requirements, use UL listed cable lugs and tools given below or
corresponding.
Wire size
kcmil/AWG
6
4
2
1
1/0
2/0
Electrical installation
Cable terminal
2
(6 to 2/0 AWG) can be connected to the screws with
Compression lug
Manufacturer
Burndy
YAV6C-L2
Ilsco
CCL-6-38
Burndy
YA4C-L4BOX
Ilsco
CCL-4-38
Burndy
YA2C-L4BOX
Ilsco
CRC-2
Ilsco
CCL-2-38
Burndy
YA1C-L4BOX
Ilsco
CRA-1-38
Ilsco
CCL-1-38
Thomas & Betts 54148
Burndy
YA25-L4BOX
Ilsco
CRB-0
Ilsco
CCL-1/0-38
Thomas & Betts 54109
Burndy
YAL26T38
Ilsco
CRA-2/0
Ilsco
CCL-2/0-38
Thomas & Betts 54110
2
(3/0 to 350 AWG) are connected to
WARNING! If the wire size is less than
95 mm
be used. A cable of wire size less than
95 mm
terminal will loosen and may damage
the drive.
Type
Manufacturer
Burndy
Ilsco
Burndy
Ilsco
Burndy
Ilsco
Ilsco
Burndy
Ilsco
Ilsco
Thomas & Betts
Burndy
Ilsco
Ilsco
Thomas & Betts
Burndy
Ilsco
Ilsco
Thomas & Betts
2
(3/0 AWG), a cable lug must
2
(3/0 AWG) connected to this
Crimping tool
Type
No. of crimps
MY29-3
ILC-10
MY29-3
MT-25
MY29-3
IDT-12
MT-25
MY29-3
IDT-12
MT-25
TBM-8
MY29-3
IDT-12
MT-25
TBM-8
MY29-3
IDT-12
MT-25
TBM-8
1
2
1
1
2
1
1
2
1
1
3
2
1
1
3
2
1
1
3