Combined braking cycles for R7:
Examples
P
br
P
or P
br5
br10
P
br30
P
brcont
No braking
• After P
, P
or P
br5
br10
br30
• P
, P
or P
braking is allowed once every minute.
br5
br10
br30
• After P
braking, there has to be a pause of at least 30 seconds without any braking if the subsequent braking power
brcont
is greater than P
.
brcont
• After P
or P
braking, the drive and the chopper will withstand P
br5
br10
• P
braking is not acceptable after P
br10
Combined braking cycles for R8:
Examples
P
P
, P
or P
br5
br10
br30
P
brcont
No braking
• After P
, P
or P
br5
br10
br30
allowed braking power after P
• P
, P
or P
braking is allowed once every minute.
br5
br10
br30
• After P
braking, there has to be a pause of at least 60 seconds without any braking if the subsequent braking power
brcont
is greater than P
.
brcont
All brake resistors must be installed outside the converter module. The resistors are built in an IP00 metal frame. The
2xSAFUR and 4xSAFUR resistors are connected in parallel. Note: The SAFUR resistors are not UL listed.
Resistor braking
max 5 s or 10 s
min. 30 s max 30 s
min. 30 s
braking, the drive and the chopper will withstand P
braking.
br5
max 5 s, 10 s or 30 s
br
min. 60 s
braking, the drive and the chopper will withstand P
, P
or P
.)
br5
br10
br30
max 30 s
min. 30 s
brcont
within a total braking time of 30 seconds.
br30
brcont
continuously.
min. 60 s
continuously. (P
is the only
brcont