Channels B, C And D - ABB AE/S 4.2 Product Manual

Abb i-bus eib / knx
Table of Contents

Advertisement

®
ABB i-bus
EIB / KNX
3.3.2

Channels B, C and D

Commissioning
No.
Function
3
Threshold value
As soon as the value exceeds or falls below the set threshold value, the following can be sent:
1-bit value [0/1]
1-byte value [0...+ 255]
The object value depends on the "Data type of threshold value object" parameter
(1 bit, 1 byte). The parameter can be found in the "A – Threshold 1" parameter window.
4
Modify
5
Modify
The upper and lower limit of threshold 1 can be modified using the bus.
In case of bus- and/or main voltage failure the changed threshold value limits are stored.
With a new download of the application program the threshold value limits will be overwritten.
The data type of these communication objects depends on the data type selected for the
"Output value – Channel A" communication object.
6
See communication
object 3
7
See e communication
objects 4 and 5
8
Table 5: Communication objects 3 to 8 – "Channel A"
No.
Function
9
See communication
...
objects 0...8
17
18
See communication
...
objects 0...8
26
27
See communication
...
objects 0...8
35
Table 6: Communication objects 9 to 35 – "Channels B, C and D"
Object name
Data type
Channel A threshold 1
EIS variable
DPT variable
EIS 1
DPT
1.001
EIS 6
DPT
5.001
Channel A threshold 1
EIS variable
lower limit
Channel A threshold 1
DPT variable
upper limit
Channel A threshold 2
Channel A threshold 2
lower limit
Channel A threshold 2
upper limit
Object name
Data type
Channel B
Channel C
Channel D
Flags
C, R, T
C, R, T
Flags
37

Advertisement

Table of Contents
loading

Table of Contents