ABB i-bus
EIB / KNX
Commissioning
Modify limits via the bus
Options:
no/yes
This parameter is used to define whether it is possible to Modify limits via
the bus. If yes is selected, the "Modify – Channel A threshold 1 lower limit"
and "Modify – Channel A threshold 1 upper limit" communication objects
also appear.
Note:
The value formats for these communication objects are
identical to the format set under the Send output value as
parameter in the Channel A parameter window.
The values must be sent in the same format as the output
value for the channel.
Data type of threshold value object
Options:
1 bit/1 byte [0...255]
If the 1 bit option is set for the Data type of threshold value object parameter,
the following parameters appear.
Send if threshold value falls below
Options:
Do not send a telegram
Send an ON telegram
Send an OFF telegram
Send if threshold value exceeds
Options:
Do not send a telegram
Send an ON telegram
Send an OFF telegram
Option Do not send a telegram = No reaction occurs
Option Send an ON telegram = Send telegram value "1"
Option Send an OFF telegram = Send telegram value "0"
Minimum duration of the underflow
Minimum duration of the overrange
Options:
none/5 s/10 s/30 s/1 min/5 min/10 min/30 min/1 h/6 h/
12 h/24 h
Option none = Send threshold value directly
The further time options can be used to select a minimum duration.
If the send condition reverts within the minimum duration, nothing is sent.
19