ABB i-bus
EIB / KNX
12
Commissioning
– The "In Operation - System" communication object sends an
"in operation" telegram
– The "Status byte - System" communication object sends a status byte
telegram
Maximum telegram rate
Options:
1/2/3/5/10/20 telegrams/second
To control the bus load, this parameter can be used to limit the Maximum
telegram rate per second.
Send cyclical "in operation" telegram
Options:
no/yes
Option no = Cyclical "in operation" telegram is not sent
Option yes = The "In operation - System" communication object appears
If yes is selected, the Send interval for "in operation" telegram parameter
becomes visible at the bottom of the parameter window.
Send interval for "in operation" telegram
Options:
10 min/30 min/1h/3h/6h/12h/24h
The "In operation – System" communication object is sent cyclically to
the bus after the set send interval.
In this way, Analogue Input can be monitored cyclically in order to protect
security-related installations.
The parameters for "Channel A" are described in the following section.
The explanations also apply to channels B, C and D. When the channel
is selected, 5 other parameter windows appear. The parameters for
the other sensor outputs are described in Chapters 3.2.3 and 3.2.4.