ABB i-bus
EIB / KNX
3.2.4
Parameter window
"Channel A – PT100
2-conductor technology"
Commissioning
The following section displays and describes the parameters which differ
from the description of the "Voltage, current and resistance".
The parameters apply both to PT100 2-conductor technology
– 30...+ 70 °C and to PT100 2-conductor 200...+ 800 °C. The difference
concerns the accuracy and resolution of he measuring range.
So that the measurement is not corrupted, the return conductor of
a PT100 sensor must be routed separately to the 0 V terminal and
may not be used as a return conductor for other sensors.
Abb. 18: Parameterfenster „Kanal A PT100 2-Leiter-Technik –30 ... +70 °C"
Fig. 19: Parameter window "Channel A – PT100 2-conductor technology – 30...+ 70 °C"
Use channel
Options:
no/yes
This parameter determines the use of channel A.
27