Commissioning
Send output value as
Options:
1-byte [0...+ 255]
1-byte [– 128...+ 127]
2-byte [0...+ 65,535]
2-byte [– 32,768...32,767]
2-byte [EIB floating point]
4-byte [IEEE floating point]
This parameter is used to define the format in which the Output value should
be sent. If the "1-byte [0...+ 255]" option is selected, for example, the Output
value is sent as a 1-byte value.
Note:
The setting requires the result of the calculation to be
adapted to the set format. Otherwise the result will be
truncated.
In order to guarantee full interoperability with other EIB slaves, only
a data type should be selected for the output which is permissible
for the calculated physical size in compliance with KONNEX! (Refer
to KNX manual chapter 3/7/2).
Send output value
Options:
after a change
cyclically
after a change and cyclically
This parameter is used to define how the Output value should be sent.
Option After a change = Send output value after a change
Option Cyclically = Send output value cyclically
Option After a change and cyclically = Send output value after a change and
cyclically
In the case of the after a change, cyclically and after a change and cyclically
options, further parameters appear.
Output value is sent, every
Options:
5 s/10 s/30 s/1 min/5 min/10 min/30 min/1 h/6 h/12 h/24 h
This additional parameter is used to set the interval for cyclical sending.
Output value is sent after x % deviation from the output range of input 1
Options:
1...2...100
This parameter is used to define what percentage change in the output
range of input 1 should cause the output value to be sent.
If 2 is selected as the option, the output value is sent after a 2% change
in the output range of input 1.