2Unpacking to installation

(2) CR751 controller

CAUTION
Three phase
AC200V
Primary
Earth leak -
age breaker
(NV)
Note 2)
Secondary
Note 1) Crimping swage is recommended for connecting the attachment ACIN connector (soldering is also possible)
Recommendation compression tools: 234171-1(Tyco Electronics)
Note 2) The earth leakage breaker is the customer preparation. Always use the cover below.
Recommendation: For single primary power supply ...... NV30FAU-2P-10A-AC100-240V-30mA, (Cover: TCS-05FA2)
Note 3) If necessary, as shown in the figure, connects the noise filter between ACIN terminal blocks and primary power supply.
(Recommended noise filter: SUP-EL20-ER6 *OKAYA ELECTRIC INDUSTRIES)
Fig. 2-11 : Connecting the power cable and grounding cable (CR751)
1) Please prepare the following: Leakage current breaker (with the terminal cover), cable for connecting the
primary power supply (AWG #14 (2mm
2
(3.5mm
or above).
The secondary power cable (with the ACIN connector) for single phase or three phase power is supplied
with the product to match the specifications. When you build a cable suitable for your environment using
the ACIN connector and the ACIN terminal supplied, prepare a secondary power cable (AWG #14 (2mm
above).
2) Confirm that the primary power matches the specifications.
3) Confirm that the primary power is OFF and that the earth leakage breaker power switch is OFF.
4) Connect the secondary power cable.
a) When using the supplied power cable with the ACIN connector
Refer to
Fig. 2-11
b) When building a power cable using the ACIN connector and the ACIN terminals supplied
Connect the ACIN terminals with the secondary power cable (prepared by customers), and insert the
ACIN terminals to the ACIN connector pins with the following numbers. Crimping caulking is
recommended to connect the ACIN terminals.
For single phase: 1 and 3
For three phase: 1, 2, and 3
Connect the cable from the secondary side of the earth leakage breaker.
5) Connect this ACIN connector to the ACIN connector on the front of the controller.
6) Connect the grounding cable to the PE terminal. (M4 screw)
7) Connect the primary power cable to the primary side terminal of the earth leakage breaker.
This completes the connection of the power and grounding cables.
2-20 Installation
Use an earth leakage breaker (customer preparation) in the primary power supply
circuit of the controller to prevent short circuit.
Controller
Single phase
AC200V
<3> LINE/LOAD
<1> LINE/LOAD
<2> LINE/LOAD
For three primary power supply ....... NV30FAU-3P-10A-AC100-240V-30mA, (Cover: TCS-05FA3)
2
and connect the cable from the secondary side of the earth leakage breaker.
Controller
ACIN connector
For single phase
Grounding screw
ACIN connector
1 2 3
PE terminal
<4> LINE/LOAD
Label
Note 3)
Noise filter
or above), cables to ground the primary power supply (AWG #12
* The controller is an
example.
For three phase
Grounding screw
ACIN connector
1 2 3
PE terminal
Note 1)
ACIN connector or
power cable
(Attachment)
2
) or