15 TROUBLESHOOTING
LED
Classifi-
Error
indicator
cation of
code
of servo
errors
amplifier
2031
31
2032
32
Servo
amplifier
errors
2033
33
2034
34
Error name
Overspeed
Speed has exceeded the
instantaneous permissible speed.
Current that flew is higher than the
Overcurrent
permissible current of the servo
amplifier.
Converter bus voltage exceeded
Overvoltage
400VDC.
CRC error
SSCNET cable communication fault
Description
15 - 38
MELSEC-Q
Cause
Parameter Pr.103 to Pr.105
setting error.
Fault in the encoder.
Output U, V, W phases of the servo
amplifier were connected with each
other.
Transistor of the servo amplifier
damaged.
Short circuit in the servo amplifier
output U, V, W phases.
Noise entered the overcurrent
detection circuit.
Lead of built-in regenerative brake
resistor or regenerative brake option
is open or disconnected.
Though the regenerative brake
option is used, the DRU parameter
" Pr.102 Regenerative brake
resistor" setting value is "0 00 (not
used)".
Regenerative brake option is open
or disconnected.
Regenerative transistor faulty.
Wire breakage of built-in
regenerative brake resistor or
regenerative brake option.
Capacity of built-in regenerative
brake resistor or regenerative brake
option is insufficient.
Power supply voltage high.
The SSCNET cable is
disconnected.
Bus cable fault.
Noise has entered the bus cable.
The terminal connector is
disconnected.
The same No. exists in the servo
amplifier side axis setting.

Hide quick links: