CHAPTER 7: COMMANDS AND TARGETS
FIRMWARE LOCK
•
Message: "Unauthorized firmware attempt"
•
Latched target message: No.
•
Description of problem: A firmware upgrade operation was attempted while the lock relay setting was enabled.
•
What to do: Ask the Supervisor to unlock the relay and try again.
SETTING LOCK
•
Message: "Unauthorized setting write"
•
Latched target message: No.
•
Description of problem: A setting write was attempted while the lock relay setting was enabled.
•
What to do: Ask the Supervisor to unlock the settings and try again.
SERVER UNAVAILABLE
•
Message: "An attempt to contact the Radius server has failed"
•
Latched target message: No.
•
Description of problem: The RADIUS authentication server is unavailable.
•
What to do: Verify network connectivity and try again.
DOS PARTITION ALARM:
SELF-TEST ERROR
•
Description of problem: There is a problem with the Compact Flash memory in the CPU module.
•
How often the test is performed: On relay power-up and afterwards once every 24 hours.
•
What to do: Contact the factory.
PROTOTYPE FIRMWARE:
Self Test Error
•
Description of problem: Seen until the builds is tagged as being 'release candidate' or 'gold' builds.
•
What to do: Update firmware to either of these builds.
7.2.2.4 HardFiber self-test error messages
In addition to those provided by the standard UR-series devices, the UR devices implement HardFiber self-tests. These are
listed here. Any abnormal diagnostic condition indicated by the LEDs or the critical failure relay also results in a self-test
message, so troubleshooting is described here. For other relays, such at the B95
Equipment mismatch major self-test
•
Description of problem: The number or type of installed hardware modules does not match the order code stored in
the CPU. The standard UR-series Equipment Mismatch self-test is extended to cover the possible presence of a
Process Card.
•
Severity: Protection is not available and all contact outputs and shared outputs are de-asserted.
•
What to do: Check all modules against the order code. Ensure they are inserted properly, and cycle the control power.
If a module has intentionally been added or removed use the Update Order Code command to notify the relay that the
current module configuration is correct.