Communication Protocols - GE N60 Instruction Manual

Network stability and synchrophasor measurement system
Hide thumbs Also See for N60:
Table of Contents

Advertisement

CHAPTER 2: PRODUCT DESCRIPTION
Make and carry:
for 0.2 s:
for 0.03 s:
Breaking capacity:
Specification
UL 508
Operations per
5000 operations,
interval
1 second on,
9 seconds off
1000 operations
0.5 seconds on,
0.5 seconds off
Break capability
3.2 A at L/R = 10 ms
(0 to 250 V DC)
1.6 A at L/R = 20 ms
0.8 A
L/R = 40 ms
CONTROL POWER EXTERNAL OUTPUT (FOR DRY CONTACT INPUT)
Capacity:
Isolation:
DIRECT OUTPUTS
Output points:
DCMA OUTPUTS
Range:
Max. load resistance:
Accuracy:
99% Settling time to a step change:
Isolation:
Driving signal:
Upper and lower limit for the driving signal: –90 to 90 pu in steps of 0.001

2.5.8 Communication protocols

IEC 61850
IEC 61850:
RS232
Front port:
RS485
1 rear port:
Typical distance:
Isolation:
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
30 A as per ANSI C37.90
300 A
Utility application
Industrial application
(autoreclose scheme)
5 operations
10000 operations
0.2 seconds on
0.2 seconds on
0.2 seconds off
30 seconds off
within 1 minute
10 A at L/R = 40 ms
10 A at L/R = 40 ms
100 mA DC at 48 V DC
±300 Vpk
64
–1 to 1 mA, 0 to 1 mA, 4 to 20 mA
12 kΩ for –1 to 1 mA range
12 kΩ for 0 to 1 mA range
600 Ω for 4 to 20 mA range
±0.75% of full-scale for 0 to 1 mA range
±0.5% of full-scale for –1 to 1 mA range
±0.75% of full-scale for 0 to 20 mA range
100 ms
1.5 kV
any FlexAnalog quantity
Supports IEC 61850 Edition 2.0. See the UR Family Communications Guide and its conformance
statements.
19.2 or 115.2 kbps, Modbus RTU
up to 115 kbps, Modbus RTU, DNP 3, IEC 60870-5-103
1200 m
2 kV, isolated together at 36 Vpk
SPECIFICATIONS
2
2-27

Advertisement

Table of Contents
loading

Table of Contents