ABB REB650 Manual page 69

Relion dnp, 650 series version 2.2
Hide thumbs Also See for REB650:
Table of Contents

Advertisement

1MRK 511 419-UUS A
650 series 2.2 ANSI
Point list manual
3.9 ANALOG INPUTS
Capabilities
Static (Steady-State)
(leave tick-boxes blank if
Group Number: 30
this data type is not
Static Frozen Group
supported)
Number: 31
Event Group Number: 32
Frozen Analog Input
Event Group Number: 33
Deadband Group
Number: 34
● Always
○ Never
○ Only if the point is
assigned to a class
○ Based on point Index
(add column to table in
part 5)
3.9.5 How Deadbands are set:
○ A. Global Fixed
○ B. Configurable
through DNP
○ C. Configurable via
other means
● D. Other, explain: Any
deadbanding is a
property of the IED's
underlying data, and is
configured through the
IED configuration tools
(PCM).
○ Based on point Index
- column in part 5
specifies which of the
options applies, B, C, or
D
3.9.6 Analog Deadband Algorithm: simple - just compares the difference from the previous reported value
integrating - keeps track of the accumulated change other - indicating another algorithm
○ Simple
○ Integrating
● Other, explain: Any
deadbanding is a
property of the IED's
underlying data, and is
configured through the
IED
○ Based on point Index
(add column to table in
part 5)
3.9.7 Static Frozen Analog Input Variation reported when variation 0 requested or in response to Class
polls:
Table continues on next page
DNP3 protocol implementation
Current Value
If configurable, list
methods
PST or LHMI
PST or LHMI
Section 3
63