Function name
Signal type
SMPPTRC
Binary inputs
SSCBR
Binary inputs
Counter
SSIMG
Binary inputs
SSIML
Binary inputs
SXCBR
Analog inputs
Binary inputs
Counters
Double bit indications
SXSWI
Analog inputs
Binary inputs
Counters
Double bit indications
T3WPDIF
Binary inputs
Table continues on next page
650 series 2.2 ANSI
Point list manual
Signal name
Description
COUNTAR
Counting total number of reclosing shots
CLLKOUT
Circuit breaker lockout output (set until reset)
TR1P
Tripping single-pole
TR2P
Tripping two-pole
TR3P
Tripping three-pole
TRIP
General trip output signal
TR_A
Trip signal from phase A
TR_B
Trip signal from phase B
TR_C
Trip signal from phase C
CBLIFEAL
Remaining life of CB reduced to Life alarm level
GPRESALM
Pressure below alarm level
GPRESLO
Pressure below lockout level
SPCHALM
Spring charging time has crossed the set value
NOOPER
Number of CB operation cycle
PRES_ALM
Pressure below alarm level
PRES_LO
Pressure below lockout level
TEMP_ALM
Temperature above alarm level
TEMP_LO
Temperature above lockout level
LVL_ALM
Level below alarm level
LVL_LO
Level below lockout level
TEMP_ALM
Temperature above alarm level
TEMP_LO
Temperature above lockout level
EEHEALTH
External equipment health. 1=No warning or alarm, 2=Warning, 3=Alarm
CLOSEPOS
Apparatus closed position
OPENPOS
Apparatus open position
UPD_BLKD
Update of position indication is blocked
CNT_VAL
Operation counter value
POSITION
Apparatus position indication
TR_POS
Truck position indication
EEHEALTH
External equipment health. 1=No warning or alarm, 2=Warning, 3=Alarm
CLOSEPOS
Apparatus closed position
OPENPOS
Apparatus open position
UPD_BLKD
Update of position indication is blocked
CNT_VAL
Operation counter value
POSITION
Apparatus position indication
BLK2H
Common second harmonic block signal from any phase
BLK5H
Common fifth harmonic block signal from any phase
INTFAULT
Indication that internal fault has been detected
OPENCTAL
Open CT Alarm output signal. Issued after a delay ...
TRIP
General, common trip signal
TRIPRES
Trip signal from restrained differential protection
TRIPUNRE
Trip signal from unrestrained differential protection