Install Software; Enervista Communication Overview - GE M60 Instruction Manual

Motor protection system
Hide thumbs Also See for M60:
Table of Contents

Advertisement

INSTALL SOFTWARE

To activate the relay using EnerVista software:
1.
Navigate to Settings > Product Setup > Installation and change the Relay Settings field to "Programmed."
2.
Save the change.
3.6 Install software

3.6.1 EnerVista communication overview

The EnerVista UR Setup software communicates to the relay via the faceplate RS232 port or the rear panel RS485 /
Ethernet ports.
3
To communicate via the faceplate RS232 port, use a standard straight-through serial cable. Connect the DB-9 male end to
the relay and the DB-9 or DB-25 female end to the computer COM2 port as described in the CPU Communication Ports
section earlier in this chapter.
To communicate through the M60 rear RS485 port from a computer RS232 port, the GE Digital Energy RS232/RS485
converter box is required. This device (catalog number F485) connects to the computer using a straight-through serial
cable. A shielded twisted-pair (20, 22, or 24 AWG) connects the F485 converter to the M60 rear communications port. The
converter terminals (+, –, GND) are connected to the M60 communication module (+, –, COM) terminals. See the CPU
Communication Ports section in chapter 3 for details. The line is terminated with an R-C network (that is, 120 , 1 nF) as
described in this chapter.
3-42
Figure 3-49: Relay communication options
CHAPTER 3: INSTALLATION
M60 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL

Advertisement

Table of Contents
loading

Table of Contents